Voltage Sag Test
Equipment - The Porto-Sag

Since
1994, EPRI's Porto-Sag line of voltage sag generators
have developed a proven reputation to be more versatile and
user friendly than any other brands on the market. Our 200 Amp
units have been in production since September 2001. |
|
The Porto-Sag PS200-3P-T is built into a rolling vertical rack
for easy transportability in lab or manufacturing environments.
Utilizing up to three
transformers, our units can create voltage sags that model
"real life" events, not just test to a given standard. This is
important when you want to make sure your equipment can
ride-through voltage sags that have been recorded in past
events. Unlike other units, the Porto-Sag allows the user to
record and view the voltage sag data immediately. We are now shipping a
Tri-Mode option for our standard 200A product.
Our Porto-Sag line is built to conform to IEC 61000-4-11, 61000-4-34, and
SEMI F42/SEMI F47 and the revised SEMI F47-0706.
Specification sheets for the 200 amp version can be downloaded below.
Three
Phase, 200A, 277/480V, with Tri Mode
Options (PS-200-3P-T)
|
Test Vector
Summary for Porto-Sag Model PS-200-3P-T and
Options |
|
Test Vector
Types |
Model |
Voltage Sag Test
Vectors |
Resolution |
Maximum
Voltage |
Swell |
|
|
Base
Model
|
A,
D, E, F |
5%
steps |
277V
L-N 480V L-L Requires
Neutral |
Up
to 125%
|
|
Tri-Mode
Option
-TM |
A,B,C,D,E,F |
10%
steps for Method C
5%
steps for all Other Methods |
277V
L-N 480V L-L Neutral Not
Required |
Up
to 120% for Method C
Up
to 125% for all Other
Methods | |
|
Voltage Sag Vector Cross Reference
|
| Vector Type |
Voltage Sag Description |
Other Common Designators |
IEC 61000-4-34 Reference Figure |
| A |
Single-Phase |
Type I |
Figure 3A |
| B |
Phase-to-Phase, Alternative 1 |
Type II.A1 |
Figure 3B |
| C |
Phase-to-Phase |
Type II |
Figure 3C |
| D |
Phase-to-Phase, Alternative 2 |
Type II.A2 |
Figure 3D |
| E |
Unbalanced Three-Phase |
N/A |
N/A |
| F |
Balanced Three-Phase |
Type III |
N/A |
|
| |
Typical Specifications for Porto-Sag Model PS-200-3P-T
|
|
|
|
|
Control
voltage |
90
to 264 VAC |
|
Operating frequency |
50
or 60 Hz, automatic
detection |
|
Test
voltage range |
100–277 V Phase-to-Neutral,
480
V Phase-to-Phase |
|
Max
load current |
200
Arms continuous |
|
Max
load inrush current |
1800
Apeak for ½ cycle |
|
Input
configuration |
3-phase Y (requires Neutral for base
mode)
3-Phase Y or Delta with Bi or Tri Mode
options |
|
Output
configuration |
3-phase Y or delta |
|
Power
consumption |
800
mA @ 120V |
|
Monitoring points |
Phase A, B, C (fused at 300 mA),
N |
|
|
|
|
|
|
|
Sag duration |
¼
cycle to 3 sec. in ¼-cycle
steps |
|
Sag magnitude |
100%
to 0% in 5% steps |
|
Swell magnitude |
+5%
to +25% in 5% steps |
|
Point-on-wave |
360°
in 1° increments |
|
Trigger output |
TTL
compatible |
|
|
|
|
|
|
|
Sampling rate |
5
kHz or 10 kHz user
selectable |
|
Resolution |
12
bits |
|
Max input voltage |
Ch
1-8: ±10 Vpeak AC or
DC |
|
|
Ch
9-16: ±700 Vpeak AC or DC (approx 480
Vrms) | |
|
|
Features |
Screen
Snapshots (Click images to see larger
snapshot) |
|
The
Porto-Sag simplifies voltage sag testing by integrating the
sag generator hardware and data acquisition software into one
package. Key features include:
|
|